GUTOR UPS PxW
|
Gutor PxW 购买价格:0.00 点击次数:2394221 发布时间:2013-05-10 21:45:22 |
Gutor PxW
Highly customizable double-conversion UPS systems
Highly flexible industrial AC UPS
Technical information
Type |
Gutor PxW 1000 (single phase) |
Gutor PxW 3000 (three phase) |
Ratings |
5-200 kVA (Higher ratings upon request) |
10-220 kVA (Higher ratings upon request) |
Operating temperature |
- 10 to +40 °C (max. 55 °C on request) |
Allowable air humidity |
< 95 % (non condensing) |
Noise level |
60 – 75 dBA (depending on rating) |
Communication protocols |
Modbus RTU, Webpage (HTTP), Modbus TCP, IEC 61850 (others on request) |
Input |
Rectifier |
6-pulse thyristor bridge (12-pulse on request) |
Voltage |
3 x 380 / 400 / 415V (other voltages on request) |
Voltage tolerance |
''+/- 10% for DC in tolerance -15/+10% for function |
Battery circuit |
Nominal voltage |
110 / 125 / 220 / 400VDC |
Applicable batteries |
Lead Acid, Nickel Cadmium |
Output |
Voltage |
220 / 230 / 240V (others on request) |
380 / 400 / 415V (others on request) |
Tolerance (static) |
+/- 1 % |
Frequency stability (free running) |
< 0.01 % |
Efficiency |
up to 91% depending on type |
Distortion |
linear load: ≤ 3 % / non-linear load: ≤ 5 % |
Overload inverter |
200% / 50-100 ms, 150% / 1 min, 125% /10 min |
Overload bypass |
1000 % / 100 ms |
Features
Industrial AC UPS with ratings up to 220kVA and higher
The Gutor PxW is successfully tested under extreme environmental conditions as well as under seismic conditions. The firmware is certified according to IEC 60880 for NPP (Nuclear Power Plant) applications. With a very flexible design, it can meet nearly any requirement.
This product is best in its class, because it benefits from our focus on quality and attention to detail.
Benefits
Flexibility
Due to the fact of independent power modules, the rectifier and the inverter part of the UPS can be sized individually.
NPP qualified
The firmware is certified according to IEC 60880 for third party, and the components withstand applicable seismic requirements.
Proven reliability
Best in class Mean Time Between Failures (MTBF) within long product lifetime with minimal servicing required. Over 20,000 systems installed worldwide with excellent quality records.
Applications
- Nuclear Power Plants (NPP)
- Oil & Gas, Petrochemical (onshore, offshore, pipelines, refining, FPSO)
- Power generation, including transmission and distribution
- Chemical industry
- Other industrial applicationsGutor PXW
高度可定制的双转换UPS系统
高柔性工业交流电源
技术信息
Type Gutor PxW 1000(单相)Gutor PxW 3000(三相)
评级5-200千伏安(更高的评级要求)10-220千伏安(要求更高的评级)
操作温度- 10至+40°C(最大55°C的要求)
允许空气湿度<95%(不凝结)
噪音等级60~75 dBA(视等级而定)
通信协议Modbus RTU、网页(HTTP)、Modbus TCP、IEC 61850(其他请求)
输入
整流6-脉冲晶闸管桥(12脉冲请求)
电压3×380/400/415V(其他电压按要求)
公差中的DC电压公差“+/- 10%”
-函数的15/10%
电池电路
额定电压110/125/220/400 VDC
适用蓄电池铅酸镉镍
产量
电压220/230 /240V(其他要求)380/400 / 415V(其他请求)
公差(静态)+/- 1%
频率稳定度(自由运行)<0.01%
效率高达91%取决于类型
畸变线性负载:3%Ω/非线性负载:5%
过载逆变器200%/50-100ms,150%/1分钟,125%/10分钟
过载旁路1000% / 100毫秒
特征
额定功率220kVA及以上的工业交流UPS
Gutor PxW在极端环境条件下以及在地震条件下成功地测试。固件是根据IEC 60880认证的NPP(核电站)应用。具有非常灵活的设计,可以满足几乎所有的要求。
这种产品在同类产品中是最好的,因为它得益于我们注重质量和注重细节。
效益
灵活性
由于独立的功率模块的事实,UPS的整流器和逆变器部分可以单独地大小。
核电厂合格
固件是根据IEC 60880认证的第三方,并且部件承受适用的抗震要求。
可靠性证明
最佳的类间平均故障间隔时间(MTBF)在长的产品寿命内,需要最小的服务。20000多个系统安装在世界各地,具有优良的质量记录。
应用
-核电站(NPP)
石油和天然气、石化(陆上、海上、管道、炼油、FPSO)
-发电,包括输电和配电
化学工业
-其他工业应用